240.24(E) Overcurrent Devices Not Permitted in Locker Rooms or Showering Facilities

Revision

Change Summary

  • The NEC previously prohibited overcurrent devices in bathrooms and now they clarify and include showering facilities and locker rooms with showering facilities.

NEC®Text

Article 240 Overcurrent Protection
240.24 Location in or on Premises.
(E) Not Located in Bathrooms. Overcurrent protective devices, other than supplementary overcurrent protection shall not be located in bathrooms, showering facilities, or locker rooms with showering facilities.

Material taken from the National Electric Code. is reprinted with permission from NFPA 70., 2023 edition. National Electrical Code®, Copyright 2022, National Fire Protection Association, Quincy, MA. All rights reserved.

Expert Analysis

A revision has been made to prohibit overcurrent protective devices in all bathrooms. Also overcurrent protective devices are prohibited in showering facilities, or locker rooms with showering facilities, as they represent similar hazards.

This revision recognizes the difficulty of accessing occupied bathrooms.

Supplemental overcurrent devices are allowed.

Examples of supplemental overcurrent devices are identified in illustration below.

Figure 1

Leviton Solution

See for yourself why The Award-Winning Leviton Load Center has been called a breakthrough in Load Centers.

First — Faster Installation — Wire the entire panel at rough-in, without a single circuit breaker present. The Leviton Load Center’s all plug-on design increases job site efficiency and provides ample room for hands to move and work freely. It’s also the industry’s first intelligent residential circuit breaker system with optional Smart Circuit Breakers. Then the My Leviton app consolidates control of the Leviton Load Center’s smart circuit breakers and the Decora Smart® Wi-Fi® product lines, enabling users to seamlessly control load center activities and home lighting from anywhere in the world using their smartphone or tablet.